Arc Flash Boundary Calculator
Arc Flash Boundary (AFB) — the distance from a potential arc source within which a person could receive a second-degree burn — calculated per the IEEE 1584-2002 empirical model (208 V–15 kV) or the Ralph Lee (theoretical) method for higher voltages or quick estimates.
IEEE 1584-2002 Model
Lee Method (>15 kV / Quick Estimate)
Formula Reference — IEEE 1584-2002
Arcing Current:
log(Ia) = K + 0.662·log(Ibf) + 0.0966·V + 0.000526·G + 0.5588·V·log(Ibf) − 0.00304·G·log(Ibf) (V < 1 kV);
log(Ia) = 0.00402 + 0.983·log(Ibf) (V ≥ 1 kV)
Normalized Incident Energy:
log(En) = K1 + K2 + 1.081·log(Ia) + 0.0011·G
Incident Energy:
E = Cf × En × (t / 0.2) × (610 / D)^x cal/cm²
Arc Flash Boundary:
DB = 610 × [Cf × En × (t / 0.2) / EB]^(1/x) mm
| K (arcing current) | −0.153 open / −0.097 box |
| K1 (incident energy) | −0.792 open / −0.555 box |
| K2 (incident energy) | 0 ungrounded / −0.113 grounded |
| Cf (calculation factor) | 1.5 if V ≤ 1000 V, else 1.0 |
Formula Reference — Lee Method
For voltages above 15 kV, or as a fast theoretical-maximum estimate:
E = 793 × V × Ibf × t ÷ D² cal/cm² (V in kV, Ibf in kA, t in s, D in mm) — the theoretical maximum power condition (Ralph Lee, 1982), generally more conservative (higher) than IEEE 1584 results.
Traditional PPE Category Reference (cal/cm²)
| Category 1 | 4 cal/cm² minimum arc rating |
| Category 2 | 8 cal/cm² minimum arc rating |
| Category 3 | 25 cal/cm² minimum arc rating |
| Category 4 | 40 cal/cm² minimum arc rating |